Are you looking for Air Conditioning maintenance in Glen Ellyn, IL ? Our AC and Air Conditioning service technicians have years of experience working on Central AC Systems like yours in Glen Ellyn, IL. has service vehicles on call that are fully equipped with the tools and parts necessary to get your Cooling System back up and operating.

We offer Central Air Conditioner maintenance and maintenance agreements to keep your AC system running great. You can rely on to advise you properly and to do excellent work promptly. Ask us about maintenance agreements for your high efficiency Air Conditioner today.

We provide Air Conditioning Maintenance in Glen Ellyn, IL

We provide Air Conditioning Maintenance Agreements in Glen Ellyn, IL

Get Your Quote Today

On Arrival Met Charles And Showed Me The Thermostat , Furnace And Condenser. Inspected The Furnace And Filter. Located Condenser And Performed The AC Maintenance. During Then Maintenance I Found Dual Run Capacitor Not Meeting The Manufacturer Specs. I Advised Charles And He Approved The Replacement. After Replacing The Capacitor I Cycled The Run It And It Is Working Properly.
Charles, B. Glen Ellyn, IL
05-31-2024
Goodman SSX140361
A/C Report Clean And Check Outdoor Condenser High Pressure - 270 Low Pressure - 110 Delta T Reading 20 Contractor Resistance Reading 0 Low Voltage Wiring Check Capacitor Reading - 43/10.22 Clean Out Electrical Compartment Refrigeration Line Check - Low Side Insulation Service Valve Cap Amp Draw On Compressor - 7.78 Amp Draw On Condenser Fan - .74 Check Filter/Replace Clean Drain Test Blower Motor
Leland, L. Glen Ellyn, IL
06-15-2020
A/C Report: Annual A/C Preventative Maintenance: Clean And Check Outdoor Condenser High Pressure - 190 Low Pressure - 110 Ambient Temp - 55 Delta T Reading -17 Contactor Resistance Reading - No Issues Low Voltage Wiring Check No Issues Capacitor Reading 45/5 @ 41.5/4.9 Replaced Cap Clean Out Electrical Compartment No Issues Refrigeration Line Check - Low Side Insulation Well Insulated Service Valve Cap No Issues Amp Draw On Compressor -5.67 Amp Draw On Condenser Fan -.72 Check Filter/Replace Air Filter Looks Good Clean Drain No Issues Test Blower Motor No Issues
Leland, L. Glen Ellyn, IL
04-11-2022
American Standard HVAC 2A6H2030B1000AA
R-22 2 Ton 3.84 Amp Draw Nominal Cooling Suggest Changing Filter To Fiber Glass Replace Cap And Hard Start Kit With Relay. Compressor Has Very High Amp Draw 13+ Amps 2.5 Ton Unit ALL Components In Very Poor Condition - Replace With High Effeceincy Furnace And AC
Tom, T. Glen Ellyn, IL
06-25-2020