A/C Report
Clean And Check Outdoor Condenser
High Pressure - 255
Low Pressure - 85
Ambient Temp - 76
Delta T Reading -18
Contactor Resistance Reading - No Issues
Low Voltage Wiring Check
Capacitor Reading 40/5@ 48.3/4.8
Clean Out Electrical Compartment Cleaned
Refrigeration Line Check - Low Side Insulation Insulation Is Good
Service Valve Cap Caps Are In Place
Amp Draw On Compressor
[email protected]
Amp Draw On Condenser Fan
[email protected]
Lock Rotor Amps -
[email protected]
Check Filter/Replace Filter Needs To Be Replaced
Clean Drain No Issues
Test Blower Motor No Issues
Furnace Report
• Inducer Amps MNF/ - Test/ 0.5
• Clean Flame Sensor Cleaned
• Blower Motor Capacitor MNF/ - Test/ No Cap/relay Good
• Inspect Wiring All Wiring Is Good
• Inspect Burner Burners Throw A Clean And Steady Flame/ No Backfire
• Inspect Orifices For Blockage No Blockages Or Kinks
• Carbon Monoxide Test No Issues
• Inspect Chimney No Issues
• Inspect Pressure Switch Lines No Blockage Or Kinks
• Test Sequence Of Operation Sequence Of Operations Is Correct.
• Inspect Heat Exchanger Heat Exchanger Is Good. Very Clean Flame
• Check Ignitor Ignitor Is Good
• Check/replace The Filter Recommend Replacing Filter/ Dirty
• Test Gas Shut Off No Issues
• Test Thermostat For Proper Operation Thermostat Turns On Call
Humidifier Maintenance And Cleaning
Disassemble And Inspect Aprilaire Humidifier
-Clean Drain Assembly
-Clean Distribution Tray
-Clean Water Feed Tube
-Verify Water Flow, Clean Orifice
-Clean Or Replace Drain Tube As Needed
-Verify 24v Control Operation
-Replace Media Filter
Set Manual Controls @ 35% For Winter Opperaion.
Verify Automatic Control Set In WiFi Stat